The Fike 100-0002 RSI is a remote status unit for the Twinflex SRP extinguishing control panel. Wired back to the panel over RS485, it shows the events the system reports, so the state of a protected area can be checked away from the panel. It does not take any detection devices of its own.
The RSI can also be used to operate the system: silence alarms, reset, sound alarms, silence the buzzer, switch to Manual Release Only mode and start a manual extinguishant release. Up to eight RSIs can be connected to one SRP panel, and all of them must sit within the 500 m maximum cable length from the panel.
| Manufacturer | Fike |
|---|---|
| Model / part number | 100-0002 (store code 100-0002//A) |
| Product type | Remote status indicator for extinguishing control |
| Compatible panel | Fike Twinflex SRP (100-0001) |
| Connection to panel | RS485 |
| Max RSIs per SRP panel | 8 |
| Max cable length | 500 m from the SRP panel (all RSIs within this length) |
| HOLD input (SW1) | Momentary normally open switch |
| RELEASE input (SW2) | Normally open switch |
| Unused switch inputs | Terminate with a 3.3 kΩ end-of-line resistor |
| Detection devices | None connect to the RSI |
Fire alarm systems should be designed, installed and commissioned by a competent person.
| Product Code | 100-0002//A |
|---|---|
| Manufacturer | Fike |
| Product Type | Intruder & Smoke Alarm |
| Technology | 2-wire (Twinflex) |
| Device Type | repeater panel |