The Fike 507-0060 is the software disk for Fike's Quadnet and Duonet addressable fire alarm systems. It carries Quadnet / Duonet OSP, the Windows program engineers use to configure these panels and their loop devices from a PC. The same program runs both panel types.
Fike's OSP operating instructions describe how the software sets detection modes, follow-on actions and individual sound patterns, handles up to three alarm stages with zone-to-zone and point-to-point cause and effect, and produces configuration and event log reports. The PC connects to the USB port on the control panel with a USB interface lead.
| Manufacturer | Fike |
|---|---|
| Model / part number | 507-0060 (507/0060) |
| Product type | Software disk |
| Software | Quadnet / Duonet OSP |
| Compatible systems | Fike Quadnet and Duonet addressable fire alarm panels |
| Platform | Windows PC |
| Panel connection | USB interface lead from PC to panel USB port |
| RoHS | Exempt |
Fike's V3.0x instructions state that OSP version 3.xx must not be used with panels running firmware earlier than V3.00, so check the panel version before programming.
Fire alarm systems should be designed, installed and commissioned by a competent person.
| Product Code | 507/0060 |
|---|---|
| Manufacturer | Fike |
| Product Type | Accessories & Mounts |
| Technology | Addressable |
| Device Type | software |
We provide tailored support for you and your CCTV system.
Many of our Cameras and Recorders come with a comprehensive 3 year warranty.
We've got a fully functioning show room and IP suite to show you exactly how our CCTV equipment works
As cheap as £10, orders placed before 2:30pm are dispatched for delivery within 1–2 working days!